logo  ST. CHARLES PARISH, LA
File #: 1999-5003    Version: 1 Name: Subdivision Regulations be amended to reflect changes in resubdivision regulations and administration.
Type: Ordinance Status: Enacted
File created: 11/15/1999 In control: Parish Council
On agenda: 12/6/1999 Final action: 12/6/1999
Enactment date: 12/6/1999 Enactment #: 99-12-7
Title: An ordinance of the Parish of St. Charles, providing that the Code of Ordinances, Appendix C, the St. Charles Parish Subdivision Regulations of 1981, Parish of St. Charles, State of Louisiana, be amended to reflect changes in resubdivision regulations and administration.
Sponsors: Chris A. Tregre, Department of Planning & Zoning, Department of Waterworks
Indexes: P and Z (Dept. of), Subdivision Regulations
Code sections: Appendix C. IV. - Design standards
Attachments: 1. PZO-99-33 minutes.doc, 2. 1999-5003 Final Ord 99-12-7
INTRODUCED BY:      CHRIS TREGRE, PARISH PRESIDENT
                  (DEPARTMENT OF PLANNING AND ZONING
                   DEPARTMENT OF WATERWORKS)
ORDINANCE NO._________
Title
An ordinance of the Parish of St. Charles, providing that the Code of Ordinances, Appendix C, the St. Charles Parish Subdivision Regulations of 1981, Parish of St. Charles, State of Louisiana, be amended to reflect changes in resubdivision regulations and administration.
Body
WHEREAS,      the St. Charles Parish Code of Ordinances, Appendix C, St. Charles Parish Subdivision Regulations of 1981 sets forth the requirements for subdivision development in St. Charles Parish; and,
WHEREAS,      the Department of Planning and Zoning and the Department of Waterworks requests changes in Appendix C, St. Charles Parish Subdivision Regulations of 1981 in order to promote adequately planned and developed subdivisions in St. Charles Parish; and,
WHEREAS,      in order to promote the health, safety, and welfare of residents of St. Charles Parish with respect to waterworks impacts due to subdivision construction within buildable land areas in St. Charles Parish; and
WHEREAS,       the St. Charles Parish Council desires to enforce Appendix C, St. Charles Parish Subdivision Regulations of 1981.
THE ST. CHARLES PARISH COUNCIL HEREBY ORDAINS:
                      SECTION I. That the St. Charles Parish Code of Ordinances, Appendix C, St. Charles Parish Subdivision Regulations of 1981, is hereby amended as follows:
Italics language to be added
         Underlined language to be amended
 
Section IV,C.,1.,c.  Water Main Looping
Revise the sentence to read as follows:
… including existing mains, shall be looped when practical to two (2) separate sources of water.
 
Section IV, C., 1., d.  Fire Hydrants
Revise the 4th sentence as follows:
Hydrants shall have proper bury length so that the bottom of the safety flange is between five (5) inches and eight (8) inches above finished grade level.
 
Revise the 7th sentence as follows:
Hydrant valves shall be a minimum of three (3) feet from hydrants located along a highway or thoroughfare and shall be valved.
 
Add the following to existing paragraph:
Hydrants that require valves shall be connected to a mechanical joint x flanged tee.
See Detailed Specifications Section for hydrant installation details.
 
 
Section IV, C., 1., e.   Pipe
Revise 6th paragraph, sentence 2 as follows:
Required horizontal or vertical defection shall not exceed 75% of the maximum recommended by the pipe manufacturer.   See Detailed Specifications Section for pipe deflection diagrams and charts.
 
Revise 7th paragraph as follows:
Hot taps made by the subdivider on existing water mains shall be made with a Mueller
CL 12 or C1-36 tapping machine or better quality as determined by the Director of Waterworks.
 
Revise 8th paragraph as follows:
All plugs, tees, bends, and hydrants shall have .....
 
Add to 9th paragraph the following:
A tracer wire shall also be attached directly to the pipe, all fixtures and appurtenances.  The tracer wire will be run to the top of each valve box to allow direct connection to the wire.
 
Completely rewrite 10th paragraph as follows:
Radial clearance between parallel water and sewer lines shall be not less than six (6) feet radial distance from water lines.  In the event that sewer lines cross water mains, sewer lines must be at least eighteen (18) inches below water main at a 90 degree crossing.  No utilities shall be installed directly above the water lines running parallel or closer than three (3) feet to the center of the water main.
 
Section IV, C., 1., f.  Meter Service Lines
Make corrections on 2nd and 3rd sentences in paragraph:
Curb stops shall be Mueller H-15166, or approved equal.  Copper tubing conforming to AWWA C800 or polyethylene tubing 200 psi PE3408 or equal conforming to AWWA ..
 
Section IV, C., 1., g.   Backflow Preventer
Revise existing 2nd sentence as follows:
..... and larger, and all industrial customers .....  See approved backflow preventer types in Detailed Specifications Section.
 
Section IV, C., 3.   Construction Inspection
Revise 4th sentence as follows:
Required pressure and leakage tests shall be witnessed by the inspector and by Department of Waterworks' personnel.
 
Section IV, C., 4.   Testing and Disinfecting Water Lines
Revise as follows:
Flushing, pressure tests and leakage tests for ductile iron,  polyethylene, and PVC ....
 
 
Section IV, C., 4., a.   Flushing
Add to existing paragraph:
Flushing shall be accomplished through a stand pipe of the same diameter of the newly installed water main.
Department of Waterworks' personnel shall be present prior to any flushing.
The contractor will be allowed four times the volume of water in the pipe being laid for flushing purposes.  Any additional water required for flushing shall be charged to the subdivider at the current water rates.
                                                            
Section IV, C., 4., b.   Pressure Test
Add the following to the beginning of the paragraph:
Department of Waterworks' personnel shall be present prior to the commencement of any pressure test.
 
Revise the existing 1st sentence as follows:
....to a hydrostatic pressure test and leakage test of one hundred and twenty pounds per square inch (120 psi)  for not ....
 
Revise the existing 2nd sentence to read as follows:
Water lines being pressure tested can only be connected to a Department of Waterworks line by the use of a reduced pressure backflow assembly.
 
Revise existing 5th sentence as follows:
After the test pressure of one hundred and twenty pounds per square inch (120 psi) has been obtained, the subdivider shall verify that all valves in the section being tested are open completely and then they may commence the leakage test in accordance with AWWA C605-94 standards.
 
Revise existing last sentence in paragraph as follows:
.... hydrostatic pressure of one hundred and twenty pounds per square inch (120 psi) .....
 
Section IV, C., 4., c.   Leakage Test
Replace the 2nd, 3rd, and 4th sentences as follows:
Leakage shall be defined as the quantity of water that must be supplied into the pipe section being tested to maintain a pressure within five pounds per square inch (5 psi) of the specified leakage test pressure after the pipe has been filled with water and the air in the pipeline has been expelled.  No installation will be accepted if the leakage is greater than that determined by the formula:
      L = (ND X Square Root of P) Divided by 7,400
 
Where:       L = allowable leakage, in gallons per hour
            N = number of joints in the length of pipeline tested
            D = nominal diameter of pipe, in inches
            P = average test pressure during the leakage test, in
                    pounds per square inch (gauge)
Leakage gallons per hour = (# of joints) X (Pipe Diameter) X (.00148)
All pressure and leakage tests are performed at one hundred and twenty pounds per square inch (120 psi).
 
Revise 5th sentence as follows:
..... Waterworks line by the use of a reduced pressure backflow assembly.
 
Revise 6th sentence as follows:
..... pressure of one hundred and twenty pounds per square inch (120 psi).
 
Revise 9th sentence as follows:
..... within the limit of 0.00148 gallons per .....
 
Section IV, C., 4., d.   Disinfecting
Revise 1st sentence as follows:
..... shall be disinfected by the Department of Waterworks at the subdivider's expense.
 
Correct the 2nd sentence as follows:
..... AWWA Standard C651.
 
Section IV, C., 4., e.   Chlorine Application
Revise the last sentence as follows:
Valves and hydrants in the lines .....
 
Section IV, C., 5., b.  Materials Specifications
Add the following after the 2nd sentence:
Only blue colored PVC pipe shall be used for underground installation.
 
Section IV, C., 5.   Materials Specifications
Add the following:
p.   Sprinkler Systems
Sprinkler system installations must have a reduced pressure detector assembly Hersey Model 6 CM-RPDA or a Watts 909 RPDA, bronze or epoxy coated, installed in the main line.  A Sensus SR 5/8 inch x 3/4 inch meter must be installed across the check valve and routinely read to detect any unauthorized usage on the sprinkler line.  This meter will be installed, read and billed the minimum rate only, at the customer's expense.  A complete set of drawings of a proposed sprinkler system installation must be submitted to the Department of Waterworks for approval.  All taps, tie-ins and installations will be made at the customer's expense.  See Detailed Specifications Section for sprinkler system installation requirements.
 
A Diagrams and Detailed Specifications Section is proposed as Section VI.   Detailed Diagrams and Specifications.
 
 
- Fire Hydrant Detail
- Canal Crossing Casing Drawing
- PVC Casing Diagram
- Reduced Pressure Backflow Specifications and Diagram
- Sprinkler System Specifications and Diagrams
- Pipe Deflection Diagrams and Charts
 
These detailed specifications will be referenced in the written body of the regulations.
NOW THEREFORE BE IT ORDAINED, THAT WE, THE MEMBERS OF THE ST. CHARLES PARISH COUNCIL, provide that the St. Charles Parish Code of Ordinances, Appendix C, St. Charles Parish Subdivision Regulations of 1981, be amended.
Vote
      The foregoing ordinance having been submitted to a vote, the vote thereon was as follows:
 
 
 
 
      And the ordinance was declared adopted this _______ day of _________, 1999, to become effective five (5) days after publication in the Official Journal.
 
 
CHAIRMAN:______________________________________________
SECRETARY:_____________________________________________
DLVD/PARISH PRESIDENT:_________________________________
APPROVED:______________ DISAPPROVED:__________________
 
 
PARISH PRESIDENT:______________________________________
RETD/SECRETARY:_______________________________________
AT:_______________RECD BY: _____________________________